Same piece of copper , from the same stick for the 2nd go around? No sir used a new stick of 2 1/2 specifically to rule that out
She never made it past the bedroom door, what was she aiming for...? She's gone shootin..
|
|
|
|
Joined: Mar 2012
Posts: 5,653 Likes: 5
Campfire Tracker
|
OP
Campfire Tracker
Joined: Mar 2012
Posts: 5,653 Likes: 5 |
Suction side of pump or discharge ? Chlorine and Copper usually not a good combo in most Water treatment feed lines I have been around most were Schedule 80 PVC with glues that rated for chlorine. Looks like cavitaion to me the 90 is not helping. Just a guess. If its disharge on the pump any air bleeds installed? Discharge side of pump. And yes the 90 is close but again the location and specific nature of the pitting is what’s curious. I have seen the harsh effect of oversized circ pumps on copper systems many times at my sites and this just doesn’t match up
She never made it past the bedroom door, what was she aiming for...? She's gone shootin..
|
|
|
|
Joined: Mar 2012
Posts: 5,653 Likes: 5
Campfire Tracker
|
OP
Campfire Tracker
Joined: Mar 2012
Posts: 5,653 Likes: 5 |
Was the 90 ell replaced both times or not all all? You reaming all cuts?
Any chance a gob of solder or a burr from the cut was left behind?
That's erosion from some source that close to the ell.
If it was electrolysis or chemical, It would be appearing in other areas also. Kenneth all fittings and pipe were replaced. Reamed proper and no chance of a burr as I’m anal x10 about fitting/pipe prep... I’m sure you understand that I’ll check for a gob of solder but man I’m pretty careful about that as well.. I agree that the easy answer is electrolysis or chemical but it just doesn’t add up to me... Some harsh and very localized turbulence seems most likely to me but I’m reaching for the why and how
She never made it past the bedroom door, what was she aiming for...? She's gone shootin..
|
|
|
|
Joined: Mar 2009
Posts: 1,858 Likes: 3
Campfire Regular
|
Campfire Regular
Joined: Mar 2009
Posts: 1,858 Likes: 3 |
As others have said, electrolysis is what I would say your problem is. I would be looking to see if there is stray current on the piping by putting a volt meter on it to ground and see what you got. I would also put dielectric gasket kits on the pump flanges if the pump is cast iron.
|
|
|
|
Joined: Mar 2007
Posts: 9,212 Likes: 3
Campfire Outfitter
|
Campfire Outfitter
Joined: Mar 2007
Posts: 9,212 Likes: 3 |
HC..I’m on board with what you’re saying, but I just don’t know how to do it.. Can you walk me thru (plumber) specifically how I would check These things with my meter “go across the piping on both sides of the pump with impedance” .....mostly this part Thanks Checking for continuity across the pump piping and check for voltage while you're at it.
I would not buy something that runs on any kind of primer given the possibility of primer shortages and even regulations. In fact, why not buy a flintlock? Really. Rocks aren't going away anytime soon.
|
|
|
|
Joined: Dec 2004
Posts: 9,743 Likes: 15
Campfire Outfitter
|
Campfire Outfitter
Joined: Dec 2004
Posts: 9,743 Likes: 15 |
I suspect there is at least a contributing issue with the volute/impeller being imperfect and causing cavitation and flow issues... I was told the pump seal had failed a while back (less than a year old) and the impeller was in bad shape and replaced as well at that time. I heard the impeller housing was not in great shape and getting the new impeller in was “tricky”. Obviously that’s not good..
If both units are cloned, swap the pumps and see if your issue transfers to the other boiler.
|
|
|
|
Joined: Dec 2014
Posts: 303
Campfire Member
|
Campfire Member
Joined: Dec 2014
Posts: 303 |
Was it determined what caused the failed seal, and impeller and housing to be in bad shape?
|
|
|
|
Joined: Nov 2018
Posts: 17,064 Likes: 12
Campfire Ranger
|
Campfire Ranger
Joined: Nov 2018
Posts: 17,064 Likes: 12 |
Some years ago I was involved in the construction of two community swimming pools. When the swimming park opened one of the pools was slowly corroding the pool ladders, fixtures, and plumbing and swimmers would report a tingling sensation when entering and exiting the pool. Inspectors closed the pool and spent tons of money trying to pinpoint the problem.
Turns out it was a defective underwater pool light electrifying the entire system.
Not saying this is the cause of your issue but something to consider.
|
|
|
|
Joined: Mar 2012
Posts: 5,653 Likes: 5
Campfire Tracker
|
OP
Campfire Tracker
Joined: Mar 2012
Posts: 5,653 Likes: 5 |
Was it determined what caused the failed seal, and impeller and housing to be in bad shape? It was replaced by the company under warranty and cause was not specifically determined I believe today we’re going to take the whole assembly apart and have a look
She never made it past the bedroom door, what was she aiming for...? She's gone shootin..
|
|
|
|
Joined: Mar 2012
Posts: 5,653 Likes: 5
Campfire Tracker
|
OP
Campfire Tracker
Joined: Mar 2012
Posts: 5,653 Likes: 5 |
Some years ago I was involved in the construction of two community swimming pools. When the swimming park opened one of the pools was slowly corroding the pool ladders, fixtures, and plumbing and swimmers would report a tingling sensation when entering and exiting the pool. Inspectors closed the pool and spent tons of money trying to pinpoint the problem.
Turns out it was a defective underwater pool light electrifying the entire system.
Not saying this is the cause of your issue but something to consider. Morewood thanks for that and yes it’s definitely something to consider. Interesting possibility but I’m not sure how I could even begin to check that within the parameters we operate in around here
She never made it past the bedroom door, what was she aiming for...? She's gone shootin..
|
|
|
|
Joined: Mar 2012
Posts: 5,653 Likes: 5
Campfire Tracker
|
OP
Campfire Tracker
Joined: Mar 2012
Posts: 5,653 Likes: 5 |
Volute looks great
She never made it past the bedroom door, what was she aiming for...? She's gone shootin..
|
|
|
|
Joined: Mar 2012
Posts: 5,653 Likes: 5
Campfire Tracker
|
OP
Campfire Tracker
Joined: Mar 2012
Posts: 5,653 Likes: 5 |
Intake side of impeller is destroyed
She never made it past the bedroom door, what was she aiming for...? She's gone shootin..
|
|
|
|
Joined: Dec 2014
Posts: 303
Campfire Member
|
Campfire Member
Joined: Dec 2014
Posts: 303 |
Wonderful. Now, where do the impeller pieces now reside?
|
|
|
|
Joined: Mar 2012
Posts: 5,653 Likes: 5
Campfire Tracker
|
OP
Campfire Tracker
Joined: Mar 2012
Posts: 5,653 Likes: 5 |
Stainless impeller on other boiler pump is in much better shape at approx 18 months old
She never made it past the bedroom door, what was she aiming for...? She's gone shootin..
|
|
|
|
Joined: Mar 2012
Posts: 5,653 Likes: 5
Campfire Tracker
|
OP
Campfire Tracker
Joined: Mar 2012
Posts: 5,653 Likes: 5 |
Wonderful. Now, where do the impeller pieces now reside? They’re at every plumbers favorite spot... Just pushed a little further down the line 😂
She never made it past the bedroom door, what was she aiming for...? She's gone shootin..
|
|
|
|
Joined: Dec 2014
Posts: 303
Campfire Member
|
Campfire Member
Joined: Dec 2014
Posts: 303 |
If the last repair was warranteed, it might be time to exercise it.
|
|
|
|
Joined: Jun 2016
Posts: 9,644 Likes: 2
Campfire Outfitter
|
Campfire Outfitter
Joined: Jun 2016
Posts: 9,644 Likes: 2 |
Intake side of impeller is destroyed Is this impeller #2? Today's inspection? If so, the 3 way valve up line is in a perfect position to starve or cause the pump to cavitate. I'd take a hard look at it. Proper installation, &/or faulty?
|
|
|
|
Joined: Dec 2014
Posts: 303
Campfire Member
|
Campfire Member
Joined: Dec 2014
Posts: 303 |
If this is mechanical damage, it could be caused by incorrect impeller to casing clearance. You did mention that the pump went together with difficulty.
|
|
|
|
Joined: Jul 2010
Posts: 8,510 Likes: 6
Campfire Outfitter
|
Campfire Outfitter
Joined: Jul 2010
Posts: 8,510 Likes: 6 |
Cert,
Been heating with boilers all my life. Had to change the volute on my B&G this winter, surprised to see made in China,
Couple thoughts
* bad piece of copper * stray voltage * pool water reacting with metals. May have to put in a water exchanger , like salt water boats . * kids pissing in pool.
Good luck,
Best,
Chuck
|
|
|
|
Joined: Apr 2011
Posts: 151,807 Likes: 19
Campfire Savant
|
Campfire Savant
Joined: Apr 2011
Posts: 151,807 Likes: 19 |
Can you use two 45’s instead of the 90. All of our pool boilers are piped with Sched 80 CPVC. Copper isn’t good with pool chemicals.
|
|
|
|